Meter cabinets with diazed and transfer switch

Meter cabinets with distribution in the standard version incorporates 63A incoming fuse. Transfer switch is included and inlet is 32A and placed behind a lockable door. The outgoing group consists of the 1st 63A 3-phase group and 4x 25A 3-fasgrupper. An optional kit to replace one 3-phase 25A group with 63A is available. All groups are connected to the terminals. The cabinets include cable strain relief and cable glands of rubber membrane to avoid soil moisture. Ground metal cabinet Type B with transfer switch and fuses.
E-number
2200579
Article number
352909
Type designation MMLK-B-FR 163-425
Rated current [A] 63
Rated voltage [V AC] 230/400
Frequency [Hz] 50
Degree of protection [IP] 44
Colour Antracit
Standard SS 430 01 10
Package size [pcs] 1
Width [mm] 620
Height [mm] 1460
Depth [mm] 245
Netweight [kg] 60
Materials Magnelis
Rated short-circuit cap. [kA] 25
Prepared module space 1
Prepared module space 4
Possibility to lock Yes
Incoming splitter term. [mm²] Al/Cu 50
Space for meters [pcs] 1
Transfer switch Yes
Name GROUND MET CAB TRANS SW 63 25
E-number 2200579
Article number 352909